Home >> Product >> Instrumentation Cable >> BS5308 |
BS5308 Part2 Instrumentation Cable PVC Insulated
|
VDE Ref Code |
|
PVC Sheath Version |
LSOH Sheath Version: |
RE-Y(St)Y (Overall Screen) |
RE-H (St)H(Overall Screen) |
RE-Y(St)Y PiMF(Individual Screen+Overall Screen) |
RE-H(St)HPiMF(Individual Screen+Overall Screen) |
RE-Y(St)Y-SWA(Overall Screen+Steel Wire Armour) |
RE-H(St)-H-SWA(Overall Screen+Steel Wire Armour) |
RE-Y(St)Y PiMF-SWA(Individual Screen+Overall Screen+Steel Wire Armour) |
RE-H(St)HPiMF-SWA(Individual Screen+Overall Screen+ Steel Wire Armour |
Construction |
|
Conductor:Annealed solid copper(Class 1),stranded(Class2), |
Binder tape:A 23 micron p.e.t.p.tape applied with the metallic side down in electrica contact with a 0.5 0.5mm 2 tinned copper drain wire over the p.e.t.p.binder tape. |
or fiexible(Class 5) to BS5360 . |
Core/Pair identification: . |
Collective screen: |
Multicore cables: |
Aluminium/p.e.t.p.laminated tape applied with the metallic side |
Up to 40 cores-yellow |
down in electrical contact with a 0.5mm 2 tinned copper |
.cores with black numbers |
drain wire over the p.e.t.p.binder tape. |
41-80 cores-black |
Outer protection: |
cores with black numbers |
Type 1 Extruded flame retardant PVC sheath. |
Multipair cables:Colour coded |
Type 2 Extruded PVC Type TM1 ,galvanised steel wire armour,extruded flame |
in accordance with Colour |
retardant PVC sheath. |
Code Chart 2 on page 6 |
|
Pair screens |
|
Aluminium/p.e.t.p.Laminated tape applied with the metallic |
Minimum bending radius: |
side down in electrical contact with a 0.5
mm 2
tinned copper drain wire. |
Type 1 8 x diameter. |
A 23 micron isolation tape is applied over the screening tape with a |
Type 2 12xdiameter. |
minimum 50% overlap. |
|
Voltage rating |
Temperature rating |
300 volt core to earth and 500 volt core to core at maximum |
During Operation:-40 ℃+70℃ |
temperature of 65
℃ |
During Installation:-0 ℃+50℃ |
These cables are not for direct connection to the public mains supply |